Id2 = Sd /√3UC2 = 1000MV·A/(√3×10.5KV) = 55KA (2)计算短路电路中各主要元件的电抗标幺值 1)电力系统(SOC = 1338MV·A) X1*= 1000/1338= 0.75 2)架空线路(XO = 0.4Ω/km) X2* = 0.4×4×1000/602 =0.45 3)电力变压器(UK% = 4.5) X3* = X4* = UK%Sd/100SN = 7.5×1000×103/(100×5700) = 13.2 绘制等效电路如图,图上标出各元件的序号和电抗标幺值,并标出短路计算点。 (3)求k-1点的短路电路总电抗标幺值及三相短路电流和短路容量 1)总电抗标幺值 X*Σ(K-1) = X1*+X2* = 0.75+0.45= 1.2 2)三相短路电流周期分量有效值 IK-1(3) = Id1/ X*Σ(K-1)= 9.6KA/1.2 = 8KA 3)其他三相短路电流 I"(3) = I∞(3) = Ik-1(3) = 8KA ish(3) = 2.55×8KA = 20.4KA Ish(3) = 1.51×X*Σ(K-1)8KA = 12.1KA 4)三相短路容量 Sk-1(3) = Sd/X*Σ(k-1)= 1000/1.2 = 833MVA (4)求k-2点的短路电路总电抗标幺值及三相短路电流和短路容量 K 1)总电抗标幺值 X*Σ(K-2) = X1*+X2*+X3*∥X4* = 0.75+0.45+13.2/2 = 7.8 2)三相短路电流周期分量有效值 IK-2(3) = Id2/X*Σ(K-2) = 55KA/7.8 = 7.05KA 3)其他三相短路电流 I"(3) = I∞(3) = Ik-2(3) = 7.05KA ish(3) = 2.55×7.05KA =17.98KA Ish(3) = 1.51×7.05KA = 10.65KA 4)三相短路容量 Sk-2(3) = Sd/X*Σ(k-2) = 1000/7.05= 141.8MV·A 三.短路电流计算结果: 1.最大运行方式 2.最小运行方式 第六章 导线、电缆的选择 概述 为了保证供电系统安全、可靠、优质、经济地运行,进行导线和电缆截面时必须满足下列条件: |